DLO

RHH / RHW-2 / RW90

Direct’s DLO is a heavy-duty flexible power cable designed for use within portable or fixed installations, diesel engines and motor leads, generators, battery leads, and other industrial applications, including shipyards, drilling rigs, construction, and renewable energy. DLO is UL listed RHH / RHW-2, CSA listed RW90, MSHA approved, and manufactured in the USA.

  • 24 AWG ASTM Class I Tinned Copper
  • EPDM (Inner) / CPE (Outer)
  • #8 AWG – 777 MCM
  • 600 / 1,000 / 2,000 V
  • -40°C – +90°C (Dry / Wet)
  • UL / CSA / MSHA / NFPA NEC / ASTM / FT-1, FT-2, and FT-5

Specifications

Conductors
  • Rope-lay, bunch-stranded 24 AWG ASTM Class I tinned copper
Voltage Rating
  • 600 / 1,000 / 2,000 V
Separators
  • Paper (1P) and Poly Wrap (2P)
Insulation & Jacket
  • Insulated with LSHF EPDM compound
  • Jacketed with CPE compound
Resistance Properties
  • Resistant to abrasion, crushing force, extreme temperatures, flame, impact, oil, sunlight, and water
  • UL tested 60°C oil resistant temperature rating
  • UL tested 720 hours sunlight resistance rating
Temperature Range
  • -40°C - +90°C (dry) / +90°C (wet)
Industry Approvals
  • UL 44, 1650, 2556, and 2806
  • UL Listed RHH / RHW-2
  • CSA C22.2 No. 38 and 2556
  • CSA C22.1 / CEC
  • CSA Listed RW90
  • MSHA Approved
  • FT-1, FT-2, and FT-5
  • 30-CFR-Part 7 Subchapter K
  • NFPA 70 / NEC
  • ASTM B3 or B33, B49, B172 or B174, B263
  • CMRT and Prop 65 Compliant
Available Lengths
  • Reels at 250’ / 500’ / 2,500’
  • Coils at 25’ / 50’ / 100’
  • Custom lengths available upon request
AWG / MCM SIZECONDUCTOR STRANDINGSTRAND GAUGEINNER WALLOUTER WALLOUTSIDE DIAMETERAMPACITY*
INININ
#84124.060.035.35180 A
#66324.060.035.383105 A
#410524.060.035.448140 A
#216124.060.035.503190A
#121024.075.045.598220 A
1 / 026624.075.045.640260 A
2 / 034224.075.045.688300 A
3 / 041824.075.045.748350 A
4 / 053224.075.045.818405 A
262 MCM64624.090.045.905467 A
313 MCM77724.090.045.973522 A
373 MCM92524.090.0451.028591 A
444 MCM1,11024.090.0451.098652 A
535 MCM1,33224.105.0601.233728 A
646 MCM1,59124.105.0601.319815 A
777 MCM1,92424.105.0601.408904 A
Allowable ampacity per NFPA 70 / NEC Article 400. Values are based on ambient temperature of 30°C.
Jacket Colors
  • Black (standard) Blue Green Red Yellow
Standard Legend
  • DIRECT (UL) E481911 {SIZE} DLO-HDFPC 90C DRY 90C WET 2kV FT-2 SUN RES PR-I - - - (CSA) 300528 {SIZE} RW90 -40C + 90C DRY 90C WET 1kV PR-I FT-1 VW-1 SR GR-I - - - FT-5 P-07-KA200007-MSHA
Marking Options
  • Ink Wheel
  • Ink Jet
  • Indent Wheel
  • Sequential Footage